Explanation:
The FZW33-12KV/24KV outdoor AC vacuum isolation load circuit breaker is a new product designed and manufactured using the existing mature production experience of load circuit breaker switches in China and advanced foreign technology. The load circuit breaker consists of a breaking plate, a vacuum arc extinguishing chamber, and an operating mechanism. Vacuum arc extinguishing has the advantages of strong arc extinguishing ability, reliable performance, long service life, small size, no explosion hazard, and no pollution to the environment
It complies with IEC62271-12; GB/T3814: 3.6~41.5kV High Voltage Switches, IEC61694; GB/T11122: High voltage switchgear and control gear
Technical data:
N1. |
Test Item |
Unit |
Data |
1 |
Rated voltage |
kV |
12 |
24 |
2 |
Rated current |
A |
411/631 |
411/631 |
3 |
Rated frequency |
Hz |
51/61 |
51/61 |
4 |
Rated short-time withstand current |
kA |
21 |
21 |
5 |
Rated short-circuit duration |
s |
4 |
4 |
6 |
Rated active load breaking current |
A |
411/631 |
411/631 |
7 |
Rated loop breaking current |
A |
411/631 |
411/631 |
8 |
Rated cable charging current |
A |
12 |
12 |
9 |
5% rated active load breaking current |
A |
31.5 |
31.5 |
11 |
Rated short-circuit making current |
kA |
51 |
51 |
11 |
Main loop resistance |
μΩ |
≤111 |
≤111 |
12 |
power frequency withstand voltage against the earth, between phases |
kV rms |
41 |
65 |
13 |
power frequency withstand voltage against the isolating distance |
kV rms |
48 |
79 |
14 |
Lightning impulse withstand voltage against the earth, between phases (peak) |
kV |
75 |
125 |
15 |
Lightning impulse withstand voltage against the air gap(peak) |
kV |
85 |
145 |
16 |
Mechanical life |
Times |
11111 |
11111 |
17 |
Three phase closing asynchronous |
ms |
≤5 |
≤5 |
18 |
Main contact blade pressure |
N |
521 |
521 |
19 |
Distance between electric parts and phase to earth |
mm |
≧311 |
≧611 |
21 |
Rated operating force |
N |
≤311 |
≤311 |