Rated ultimate short-circuit breaking capacity Icu of molded case circuit breaker

2025-04-07 发布者:中国·明日电气有限公司

There are two indicators for the breaking capacity of circuit breakers: rated ultimate short-circuit breaking capacity Icu and rated operating short-circuit breaking capacity Ics
The rated ultimate short-circuit breaking capacity Icu is the limit parameter of the breaking capacity of the circuit breaker. After breaking several short-circuit faults, the breaking capacity of the circuit breaker will decrease
The rated short-circuit breaking capacity Ics is a breaking indicator of a circuit breaker, which means that after breaking several short-circuit faults, it can still ensure its normal operation< For molded case circuit breakers, as long as the Ics are greater than 25% Icu, they are considered qualified. Currently, most circuit breakers on the market have Ics between (50% -75%) Icu