Product Overview
KYN61-40.5 Armored Removable AC Metal Enclosed Switchgear (hereinafter referred to as switchgear) is an indoor complete set of power distribution equipment with three-phase AC current of 50Hz and rated voltage of 40.5kV. As a power plant, substation, and industrial and mining enterprise that receives and distributes electrical energy, it plays a role in controlling, protecting, and monitoring circuits, and can also be used in places with frequent operations. This switchgear complies with
GB3906-2006, GB/T11022-1999, DL/T404-2007 and other standards
Main features
The cabinet structure adopts an assembled type, and the circuit breaker adopts a handcart floor standing structure
Equipped with a brand new composite insulated vacuum circuit breaker, which has the characteristics of good interchangeability and easy replacement
The handcart frame is equipped with a screw nut propulsion mechanism, which can easily move the handcart and prevent damage to the propulsion structure due to misoperation
All operations can be performed with the cabinet door closed
The interlocking between the main switch, handcart, and switch cabinet door adopts a mandatory mechanical locking method to meet the "five prevention" function
The cable room has ample space and can connect multiple cables
Quick grounding switch is used for grounding and closing short-circuit circuits
The protection level of the shell is IP3X, and when the handcart door is open, the protection level is IP2X
The product complies with GB3906-2006, DL/T404-2007, and adopts the international IEC298 standard as a reference
Usage conditions
Environmental temperature: upper limit+40 ℃, and the average value measured within 24 hours does not exceed 35 ℃, lower limit -10 ℃
Altitude: not exceeding 1000m
Relative humidity: daily average not exceeding 95%, monthly average not exceeding 90%
Shock resistance: not exceeding 8 degrees
Water vapor pressure: daily average not exceeding 2.2kPa, monthly average not exceeding 1.8kPa
Places without fire, explosion hazards, serious pollution, chemical corrosion, and severe vibration
Note: If ordering this product exceeds the above conditions, please consult with our company
Installation of switchgear
Height of electrical room: ≥ 4500mm
Distance from the back of the cabinet to the wall: ≥ 1500mm
Flatness of infrastructure: ≤ 1mm/m2
The height of the foundation embedded channel steel above the ground shall not exceed 3mm
Fixed on the foundation using bolts or welding methods
The weight of the switchgear is about 1800kg
Width of switchgear operating corridor (single row): ≥ 3000mm, double row (face-to-face) ≥ 4000mm
Ordering Notice
When placing an order, please indicate:
1. Main circuit scheme number, purpose, single line system diagram, arrangement diagram, and distribution room layout plan, etc
2. Schematic diagram and terminal arrangement diagram of auxiliary circuit wiring
3. The model, specifications, and quantity of electrical components inside the switchgear
4. Requirements for control, measurement, and protection functions of switchgear, as well as requirements for other locking and automatic devices
5. If a busbar bridge connection is required between switchgear or incoming cabinets, specific requirements such as the rated current carrying capacity of the busbar bridge, the span of the busbar bridge, and the height above ground should be provided
When attachments and spare parts are needed, the type and quantity should be specified
7. Switchgear used in special environmental conditions should be specified in detail when ordering